Optical-Thermal Detector
• Addressable conventional technology
• Combination of optical and thermal
characteristics of fire
• Drift compensation
• Sensitivity selectable in 3 steps
• Addressing by means of address
module or detector parameterisation
• Function testable with Remote Test
Unit ECO1000RTU
Description
The Optical-Thermal Detector 2351TEM uses both the
scattered light principle as well as a separate thermal
detection unit. It was developed to detect the charac-
teristics of fire in a wide range of applications, and to
avoid deceptive alarms. The modern design of both
measurement systems and the analysis of the parame-
ters by means of a special algorithm allow to reliably
evaluate the characteristics of fire. This makes it an
all-rounder that is used in virtually all fields of fire de-
tection.
detector addressing can be achieved in 2 ways:
• A detector with an Address Module NG58-1 can be
individually identified by the suitable control panel.
• An address, which has been stored in the detector
by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. In addition
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used
to set and display the following detector parameters:
• the sensitivity in 3 levels,
An internal drift compensation adjusts the alarm thres-
hold by continually evaluating the contamination of the
detector. With that, the sensitivity of the detector is
kept constant for a long time.
• the detector address, and
• the date of the previous maintenance.
Furthermore, the degree of drift compensation (de-
tector contamination) and the current condition of the
detector can be read out.
The thermal sensor complies with Class A1R accor-
ding to EN 54-5. The detector can therefore be used in
rooms with a maximum height of 7.5m.
The detector can be attached to various detector ba-
ses and it can be protected against theft.
Addressable conventional technology is used for alarm
transmission to the fire detection control panel. The
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
2351TEM_DBL_LST_EN_0850.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
Kuppersbusch USA Slow Cooker EKI846UL User Manual
KWC Indoor Furnishings K10C148 User Manual
Learning Resources Marine GPS System LER 3240 User Manual
LevelOne Switch GSW 2476 User Manual
Life Fitness Home Gym SODB User Manual
Lightolier Indoor Furnishings 1101HCB User Manual
Makita Computer Monitor BSS500 User Manual
Mark Of Fitness Home Gym XM 4419 User Manual
McCulloch Lawn Mower 966564001 User Manual
McCulloch Trimmer 248748 User Manual